| ⚠️ WARNING: This article is intended for qualified professional electrical installers ONLY. System owners (consumers) should NOT follow these instructions. Improper installation or handling of electrical equipment can result in serious injury, fire, or damage to your system and loss of warranty. If you are a system owner and need assistance, please contact your Emaldo® installer directly. |
|
AC input |
|
|
Rated Input Power |
10800VA |
|
Rated Input Current |
3 x 15.6A |
|
Rated Input Voltage |
400Vac |
|
Rated Input Frequency |
50/60Hz |
|
Max Input Current |
3 x 15,8A |
|
AC output (on-grid) |
|
|
Rated Output Apparent Power |
10800VA |
|
Rated Output Current |
3 x 15.6A |
|
Rated Output Voltage |
400Vac |
|
Rated Output Frequency |
50/60Hz |
|
Max Output Current |
3 x 15,8A |
|
Max Power Factor |
0.8i...1...0.8c |
|
THCv |
<3% |
|
AC Output (off-grid) |
|
|
Rated Output Apparent Power |
10800VA |
|
Rated Output Current |
3 x 15.6A |
|
Max Output Current |
3 x 15,8A |
|
Rated Output Voltage |
400Vac |
|
Rated Output Frequency |
50/60 (± 0.5)Hz |
|
PV Input |
|
|
Max Input Power |
4000W x 3 |
|
Max Input Open-circuit Voltage |
550Vdc |
|
MPPT Voltage Range |
90-500Vdc |
|
Start-up Voltage |
100Vdc |
|
Max Input Current |
3 x 14,5A |
|
Max Short-circuit Input Current |
3 x 18A |
|
MPPT Input String Number |
3 |
|
EV output |
|
|
Rated Output Power |
10800W |
|
Rated Output Current |
3 x 15.6A |
|
Rated Output Voltage |
400Vac |
|
Interface Type |
IEC Type2 (IEC62169) |
|
Leakage protection |
Integrated (external) |
|
Battery |
|
|
Battery Type |
LFP (LiFePO4) |
|
Battery Capacity (per battery) |
3072 Wh |
|
Rated Battery Voltage |
51.2V |
|
Battery Voltage Range |
40V~58.8V |
|
Max Charging Current |
100A (depend on number of batteries) |
|
Max Discharging Current
|
180A (depend on number of batteries) |
|
Efficiency |
|
|
Max Efficiency |
97.00% |
|
European Efficiency |
96.00% |
|
Protection |
|
|
Anti-islanding Protection |
Integrated |
|
Reverse Connection Protection of Photovoltaic Input |
Integrated |
|
Insulation Impedance Detection |
Integrated |
|
Residual Current Detection |
Integrated |
|
Output Overcurrent Protection |
Integrated |
|
Output Short Circuit Protection |
Integrated |
|
Output Overvoltage Protection
|
Integrated |
|
General |
|
|
Operating Temperature (Celcius) |
-20~50 °C |
|
Relative Humidity |
0~95% |
|
Altitude |
2000m |
|
Cooling |
Forced Air |
|
Noise |
<50dB |
|
Display
|
E-Ink + LED + App |
|
Communication |
RS485 (Smartmeter) |
|
4G/WiFi/Bluetooth |
YES/YES/YES |
|
Topology |
Transformerless |
|
Weight (kg) |
215 kg (Including 3 Batteries) |
|
Dimensions (W*H*D mm) |
700*1520*327 mm |
Disclaimer
The product specifications provided herein are subject to change without notice, and while we endeavor to maintain accuracy, Emaldo Power Core cannot guarantee completeness, accuracy, or reliability. Performance metrics are based on typical scenarios and actual performance may vary. Compatibility with third-party products is not guaranteed. The limited warranty terms, proper installation by a qualified electrician, and adherence to safety practices are essential. Energy data accuracy is aimed for but not guaranteed. Technical support availability varies. Emaldo Power Core is not liable for any damages from product use. Specifications and features are subject to change. Usage implies agreement to these terms. For legal compliance, consult professionals.